32 Channel Datalogger
Download Product CataloguePMPR5000ST is touch screen universal color paperless recorder, Max 32 channels, high accuracy, universal use, easy operation, to Be aimed to display, measurement the processes parameters such As temperature, humidity, pressure, flow, vibration etc in various Industrial Application.
Features:
- High accuracy: ±(0.2%FS + 1 digit)
- Display: 7’’ TFT LCD Touch Screen
- Programmable universal input: T.C., RTD, mA, VDC, mV
- Input channels: 1, 2, 3, 4, 5, 6…32 channels (optional)
- Built-in thermocouple automatic cold junction compensation
- Output: Max. 16 relay, 24 VDC feeds, retransmission (optional)
- Communication port: RS485, standard MODBUS-RTU protocol, Ethernet TCP/IP configurable with HMI, SCADA, OPC server, etc.
- Flow totalizer with temperature, pressure compensation
- Match function: +, -, x, /, average, max, min
- Display options: Various curve, barograph, digital formats for different types of displays
- PC Software: Strong software for data display in digital curve, printing, and export to Excel for further analysis
- Power supply: 100-240VAC; 24VDC
Input | |
Input No. | 1, 2, 3, 4, 5, 6, ......32, optional |
Thermocouple Input | K, J, T, E, R, S, B, N, Wre526, Wre325 |
RTD Input | Pt100, CU50, CU100; 0-400ohm |
Analog Input | 4-20mA, 0-10mA, 0-5V, 1-5V, 0-10VDC |
mV Input | 0-20mV, 0-50mV, 0-100mV, 0-500mV |
Isolation | photoelectric isolation |
Accuracy | ± (0.2%FS +1) digit |
Resolution | 0.1°C when temperature input |
Sample time | 0.5~1 second per 8 channels, independent |
Decimal No. | 0-4 programmable; 1 when temperature |
T.C. cold compensation | Built-in auto. Compensation |
Compensation Tolerance | Max. ±1°C |
Channel-GND Isolation | 1000VAC |
Channels' Isolation | 400VAC |
Temperature shift | 50PPM |
CMR Ratio | 85-110dB |
T.C. wire resistor | Less than 1000Ω |
RTD wire resistor | max1000Ω per wire, should same each wire |
Inner CPU | 32bits ARM CPU, high performance |
Hardware watchdog | CPU inner integration for long-term stability |
Input Type | Measured Range |
RTD | Pt100: -200 to 600°C; CU50: -50 to150°C; CU100: -50 to150°C |